Legionella Flushing: How Long to Run Taps and What the Rules Say
Published 14 March 2026
Flushing infrequently used water outlets is one of the simplest legionella control measures — but the detail matters. Run the tap for too short a time and stagnant water remains in the pipework. Flush without recording it and you have no evidence of compliance when an inspector asks.
Here is exactly how long to flush, which outlets need it, and how to document it properly.
How long to run taps when flushing
HSG274 Part 2 does not specify a single fixed duration. Instead, it states that outlets should be flushed until the temperature at the outlet stabilises and is comparable to the supply water temperature.
In practice, this means:
| Outlet type | Recommended minimum flush time | Why |
|---|---|---|
| Taps (hot and cold) | 2 minutes each * | Enough to clear standing water from most domestic pipe runs |
| Showers | 2 minutes with showerhead attached * | Showerheads create aerosols — flush with the head on to clear the hose as well |
| Long pipe runs (distant outlets) | 5 minutes or until temperature stabilises | Distant outlets have more standing water to clear |
* These are rules of thumb for typical domestic pipe runs. Flush longer if the temperature has not stabilised — the key test is reaching supply temperature, not a fixed time.
The two-minute guideline covers most residential and small commercial properties. For buildings with long pipe runs between the water source and distant outlets, you may need to flush for longer — check the temperature at the outlet to confirm the water is now at supply temperature.
Run both hot and cold. Flushing only the cold tap leaves hot water stagnant in the hot pipework. Both must be run.
Which outlets need flushing
Any outlet not used for seven or more consecutive days is classed as an infrequently used outlet under HSG274 and must be flushed before the next use.
Common examples:
- Vacant rental properties — every tap and shower between tenancies
- Guest rooms in hotels and B&Bs — any room not occupied for a week
- Seasonal facilities — outdoor taps, summer kitchen areas, pool showers
- Unoccupied flats in HMOs — vacant units within a shared building
- Infrequently used meeting rooms — office kitchenettes, secondary bathrooms
- School buildings during holidays — all outlets in closed wings or buildings
If you have a building where some outlets are rarely used but the building itself is occupied, those specific outlets still need weekly flushing.
How often to flush
| Scenario | Frequency |
|---|---|
| Outlet used daily | No flushing needed — regular use performs the same function |
| Outlet used at least weekly | No flushing needed |
| Outlet unused for 7+ days | Flush before next use |
| Outlet rarely used (monthly or less) | Weekly flushing schedule recommended |
| Building closed for extended period | Full system flush before re-opening, with temperature monitoring |
For properties with outlets that are consistently underused, setting up a weekly flushing schedule is simpler than tracking individual outlet usage. Flush every unused outlet at the same time each week and record it.
How to flush safely
Flushing sounds straightforward — turn on the tap and wait. But there are specific precautions:
- Minimise splashing. Legionella bacteria travel through water droplets (aerosols). Run taps gently rather than at full blast, and keep the outlet pointed into the basin or drain.
- Ventilate the room. Open windows or run ventilation while flushing showers.
- Showerheads on. Flush showers with the showerhead attached, not removed. The hose and head contain standing water that needs clearing too.
- Check temperature. At the end of the flush, check the water temperature to confirm it has reached supply temperature — hot water above 50°C at the outlet, cold water below 20°C.
Recording flushing — what to log
ACoP L8 requires records of all control measures. A flushing log should capture:
| Field | Purpose |
|---|---|
| Date and time | When the flush was performed |
| Outlet location | Which tap, shower, or outlet (room number + description) |
| Hot water flushed | Yes/No + duration |
| Cold water flushed | Yes/No + duration |
| Temperature at end of flush | Confirms water reached supply temperature |
| Person performing flush | Who carried it out |
| Notes | Any observations (discolouration, unusual smell, slow flow) |
For a property with 10 outlets, recording this on paper takes 5-10 minutes per flush cycle. Across a portfolio of properties, the paperwork adds up quickly.
What happens if you skip flushing
Stagnant water is the primary condition for legionella growth. Water sitting in pipes between 20°C and 45°C for extended periods allows bacteria to multiply. When the tap is eventually turned on — particularly a shower — those bacteria are aerosolised and can be inhaled.
The risk is not theoretical. Buildings that re-opened after extended closures without proper flushing protocols have experienced legionella growth in stagnant water systems.
From a compliance perspective, flushing records are commonly requested during compliance checks. No records means no evidence of compliance, regardless of whether you actually flushed.
Building a flushing schedule for your property
The practical steps:
- List every outlet — go room by room and record every tap, shower, and water outlet
- Identify which are infrequently used — any outlet not used at least weekly
- Set a weekly flushing schedule — same day each week, same person responsible
- Record every flush — date, outlet, duration, temperature, person
- Review the schedule when occupancy changes — new tenants, seasonal closures, building works
LegioLog's Flushing Schedule Calculator generates a recommended flushing schedule based on your building type and outlet count — including a printable checklist you can use each week.
For the full regulatory context, see our ACoP L8 and HSG274 guide.
This guide covers legionella flushing requirements under HSG274 Part 2 for England, Wales, and Scotland. This is general compliance guidance, not legal or professional advice — for site-specific flushing protocols, refer to your building's legionella risk assessment.
Sources
Keep your legionella records audit-ready
Join the waitlist for LegioLog — purpose-built compliance tracking for UK duty holders.
No spam. Unsubscribe any time. Privacy policy
Related guides
UK Legionella Testing Requirements: What the Law Says in 2026
What UK law requires for legionella testing — the difference between risk assessment, temperature monitoring, and microbiological testing, and who needs each.
Legionella Written Scheme of Control: What to Include and How to Write One
How to write a legionella written scheme of control under ACoP L8 — the 6 required sections, building-type examples, and how it connects to your risk assessment.
Do I Need a Legionella Risk Assessment? Who Must Comply and When
Who needs a legionella risk assessment in the UK — landlords, employers, care homes, schools, and other duty holders. Clear yes/no answers by building type.